Products
Rated Power up to 500 kVA
1000V 16.7-up to 800 Hz
Options
Sinusoidal input current (feedback free)
Event log
Output voltage adjustable
Output frequency adjustable
Increased short circuit current
Adjustment by:
RS-232 interface
CAN bus
Ethernet
EtherCAT
Extern operation panel
Analogue interface 0-10 V
Analogue instruments
Sensoric
Customer specific designs
TFT-Display
Technical ? Data:
Mains voltage:V 110 – 660, ±10%, (3-phase, 1-phase, 16 ?Hz)?with N or without N, 50 or 60Hz
Output ? voltage:V 10 – 750 ±1% permanent or adjustable, 1-/3-phase
Output ? frequency:Hz 15 –800 adjustable,fixed frequency 16.7, 40, 50, 60, 400, 800 Hz
Output ? frequency accuracy:% ±0,5 (for some fixed frequencies are 0,1% possible)
Rated output power:kVA 5 – 500
Voltage regulation
static ±1(fs)
dynamic ±4 at 100% load change (50/60Hz),
±8 (800Hz)
asymmetric load% ±2 at 100% unbalance load
Regulation time:msec <25
Overload characteristic:% 150% for 1 min. / 125% for 10 min. / 110% for 20 ? min.
Short-circuit characteristic 2 x I nom., at 1-phase output,
2-4 x I nom., at 3-phase output,
or 5s according EN 50091, Part 1
Waveform: sinusoidal
Distortion factor:% ≤ 5 (typical 3)
EMC: According to EN 50091-2
Permissible power factor: power derating, if power factor deviates from 0,8 ? lagging
Crest factor of the load current: ≤ 2,3 (at 100% Load)
Standard ? Design:
Permissible ambient temperature:°C 0 up to + 40
Permissible environment: 3K3 according to IEC 60721?(max. 85% rel. humidity, none condensation)
Permissible operating altitude: 1000 m above m.s.l. with rated load
Protection class: IP 20 according to IEC 60529
Paint finish: RAL 7035
Cooling: “AN” natural air cooling or??AF“ forced air cooling?depended on rated power
For your requirements / specifications we are pleased to prepare an individual system configuration.